Keep the connection open. There is no idle timeout, so one connection can
be used for all requests. Reconnect if the connection is closed, for example
when the printer restarts.
Read whole items. Start each read at the first register of an item and
end at the last register of an item. Poll only the ranges in the
mapping list.
Read coils in one block. Unmapped coils read 0, so a single read can
cover all the coils you need.
Write multi-register items in one request. Use function 16 for 32-bit and
STRING items. Do not write a 32-bit item one register at a time.
Write triggers once per event. A write to a
Select label or
Select from table item selects a job
every time. Do not include them in a cyclic write.
Use edges for latching action coils. Write 1 on the rising edge of the
PLC condition, and 0 afterwards, or use auto-clear coils.
Check the result, not the command. After running an action, read a
signal that shows its effect, such as printer.<printerID>.ready.
Handle exceptions. Treat exception 02 as a mapping error, 03 as a
rejected value and 04 as a printer-side problem. See
Exception codes.